info@prolianceuae.com +971 4 2674 920

Himel- Distributor Of Himel In Uae

Air Circuit Breaker
Main Characteristics


Frame(A):1600N, 4000H1, 4000H2, 6300L In (A):630 ~ 6300

  • Ue(V):400/415, 690
  • Poles: 3P & 4P
  • Power demand meter function (A / A III / kW III / kVA III)
  • Type: Fixed type & Draw-out type
  • Certificates: CE, KEMA
  • Standards: I EC 60947-2

Molded Case Circuit Breaker (MCCB)HDM6s

HDM6s Molded Case Circuit Breaker
Frame(A):1600N, 4000H1, 4000H2, 6300L In (A):630 ~ 6300
Basic Technical Data

  • Rated Insulation Voltage Ui: AC 800V (Frame 63AF: AC 690V)
  • Rated Impulse Withstand Voltage Uimp: 8KV (Frame 63AF: 6KV)
  • Rated Working Voltage Ue: AC 415V (Frame 63AF: AC 400)
  • Rated Working Frequency: 50Hz/60Hz
  • Utilization Category: A
  • Isolation Function: Applicable for all series

Miniature Circuit Breaker (MCB) - HDB6

Miniature Circuit Breaker

    Standard: IEC 60898-1
    Trip Curve: B, C and D curves
    Breaking Capacity: 3000/4500/6000A


Residual Current Protection Module (RCCB) HDB6VR

Residual Current Protection Module
Standard:IEC 61008-1
RCCB Type: AC, A
Sensitivity: 30, 100, 300mA

HDB6VR Residual current operated circuit breakers combine the following functions:

  • Protection for users against indirect contacts
  • Additional protection for users against direct contacts (30mA)
  • Protection for electrical installations against insulation faults (fire hazard, etc)

Switch Disconnector (R/M) Isolator HDB61S

Switch Disconnector

Standard: I EC 60947-3
HDB6IS switch disconnectors combine the following Function:

  • Making and breaking normal load circuits
  • Isolation
  • Number of poles 2,3,4
    Rating: 20-125(A)


HJX2-4P AC Contactor

AC Contactor

Standard: I EC 60947-4-1

Product Name Rated Current Main Current Coil Voltage Coil Frequency
HJX2 09 04   7
 

09:9A 12:12A
95:95A

04:4NO+0NC 08:2NO+2NC B:24V X;440V 7:50/60Hz


HLD11 Indicator Light

HLD11 Indicator Light

HLD 11 Series of indicator light provide:
Pilot signal, anticipating signals
Emergency signals and other instructions incidents signal use
Technical Data

Rated Voltage(V) AC/DCt AC
Rated Current(MA) <50 ><20>
Working Life (H)
Brightness of the Iight(cd/m2)
3000
240
 
Power Frequency withstand voltage)> 2500 VAC 1min  

Before board protect degree

IP65 > >


HLMK Series Current Transformer

HLMK Series Current Transformer
Technical Data

Standard: IEC 60044-1
Primary current: 100A-5000A
Secondary approval: 5A, 1A
Maximum voltage: 0.66kV
Class: 0.5, 1.0,3.0
Short time thermal current: lth=100lh
Rated security coefficient: FS<5




HLD11 Indicator Light


H72 & 96 Series Panel Meter

H72 & 96 Series Panel Meter (Ammeter, Voltmeter, Frequency Meter, P.F Meter)

HLD 11 Series of indicator light provide:
Pilot signal, anticipating signals
Emergency signals and other instructions incidents signal use
Technical Data

Standard I EC 60051
Dielectric strength test Frequency 50/60Hz Voltage 2000V, Duration 1 m
Impact test Max acceleration 147m/s2
Response time 4s
Angular Deflection 90
temp -25 -+40
Humidity (25%-80%)RH
Evvironment No mildew, insects, salt mist, dew in the air, few sands and dusts are permitted.
Installation Shall be installed vertically


HKG 816 Series Digital Switch

HKG 816 Series Digital Switch

Rated AC frequency of 50 Hz, rated AC control voltage 230V or below
Be used as time control components in automatic control circuit, according to the scheduled time to time -on or off the circuits.

Cover Output loops Rated control voltage
Non-transparent cover 16-on16-off AC230V HKG816B230
Transparent cover 8-on- 8-off AC230V HKG816A230


HRT Fuse Puller, 10x38 Fuse Carrier and 10x38 fuse Links


AC Contactor HDC6

HDC6 AC Contactor

Standard: IEC60947-1.IEC 60947-4-1

Product Name Rated Current Auxilary Contact Coil Voltage Coil Frequency
HDC6 09 11 M
09.9A 11:1NO+1NC B:24V Coil Frequency
09 630:630A 00:0NO+0NC X:440V 7:50/60HZ


Thermal Overload Relay HDR6

HDR6 Thermal Overload Relay

Standard: IEC60947-1.IEC 60947-4-1

Product Name Frame Current Setting Current Installation Type
HDR6 18 11 M
18:18A 630:630A P15: 0.1-0.15 630:460-630A
P means decimal point

Default: None
Independent Installation



HDP6 Motor Circuit Breaker

HDP6 Motor Circuit Breaker

Standard: I EC 60947-1,
IEC 60947-2, I EC 60947-4-1

Product Name Frame Current Setting Current
HDP6 32 P16
  32:32A P16:0.1-0. 16A 32:24-32A
P means decimal point


Miniature Relay HDZ8P

Miniature Relay

Used to implement the conversion of intermediate control signals and low-power output, In the field of industrial control, used in conjunction with contactors, relays, circuit breakers, etc.



HDCH8S Modular Contactor

  • Automatic control on Equipment in buildings
  • Switch on or Switch off lighting or other equipments

Technical Information

Standard IEC 61095  
Ambient Temperature -5C-40C  
Rated Voltage Ue 230V AC  
Rated Insulation Voltage Ui 500V AC  
Operation Time >30000 times  
Coil Volatge(Us) 220/23V AC  
Type AC-7a AC-7B
Rated Current (le) 20A/25A/32A/40A/63A 7A/8.5A/12/A/15A/25A
Rated Power 4kW/5.4kW/6.5kW/8.4KW/13KW 1.2kW/1.5kW/1.9kW 2.4W/3.8kW
Operation Frequency 1200times/h 30time/h
Making & Breaking Capacity 1.5le 8le